Ex Sockets, Switches and Control Gear
Ex sockets, switches, push buttons, control stations and isolators allow equipment to be powered and controlled directly in the hazardous area, without an electric arc at the contacts being able to ignite the atmosphere. They are made in Ex d or Ex e construction and, on sockets, include mechanical interlocks that prevent connecting or disconnecting under load, and the choice depends on the zone, the current and the number of poles.
Any contact that opens under load produces an arc, and in an explosive atmosphere this is an ignition source. For this reason, Ex control gear isolates the contacts in an Ex d flameproof chamber or places them in a construction that avoids arcing in normal operation. Ex sockets usually have an interlock device: the plug can be inserted or removed only with the contacts disconnected, and the switch cannot be closed unless the plug is fully inserted. The arc therefore occurs in a closed, protected chamber, not in the outside atmosphere.
Control stations with push buttons, selectors, indicator lamps and emergency stop buttons are configured from modules, in aluminium, stainless steel or polyester enclosures. The choice depends on rated current, voltage, number of poles, classified zone and working environment. In installations that drive motors or power equipment, Ex control gear is completed with certified junction boxes and cable glands, so that the entire electrical chain remains compliant.
How to choose
Classified zone and gas group
The gear must be certified for the zone concerned and for the substance group - IIA, IIB or IIC; the higher groups are more demanding on the flameproof joints.
Rated current and voltage
Choose with a margin over the real load, taking into account the starting current of motors and the utilisation category of the contacts.
Number of poles and configuration
Sockets and isolators come with 2, 3, 4 or 5 poles, with or without a protective conductor; match them to the supply system (single-phase or three-phase).
Mechanical interlock
On sockets, the interlock prevents connection under load; check that the plug and socket are from the same certified series.
Control station functions
Decide which push buttons, selectors, lamps and emergency stop are needed and whether additional contacts are required for automation.
Enclosure material and IP rating
Corrosive, marine or washdown environments call for stainless steel or polyester and a high IP rating; also check mechanical strength.
Cable entries and mounting
The number and thread of the entries, and the type of fixing - wall, bracket or pole - are decided from the start, for easy and compliant wiring.
What to send for a quotation
- The classified zone, gas group and temperature class
- The function: socket, switch, isolator or control station
- The voltage, rated current and number of poles
- The push buttons, selectors and lamps needed in the control station
- The material, IP rating and thread of the cable entries
- The quantity and the mounting location
Typical applications
- Powering portable machinery in Ex zones
- Local control of pumps and agitators
- Emergency stop on platforms and ramps
- Local isolation for maintenance in chemical installations
Maintenance and spare parts
Periodically check the contacts and the interlock mechanism, the condition of the gaskets and the cleanliness of the joint surfaces on Ex d enclosures. Socket covers are kept closed when not in use, to prevent dust and moisture from entering. Devices are not opened under voltage in the hazardous area without a work permit, and in case of failure they are replaced with original parts of the same certificate, not with variants that merely look similar.
Brands we quote for this product type
Frequently asked questions
Why do Ex sockets have a mechanical interlock?
Because disconnecting a plug under load produces an electric arc, and in an explosive atmosphere this could cause ignition. The interlock prevents the plug being inserted or removed while the contacts are live and allows the circuit to be closed only when the plug is correctly seated. The arc thus occurs in a protected chamber, not in the outside atmosphere. The socket and plug must come from the same certified series.
Can I install Ex switches in zone 2 if they are certified for zone 1?
In general yes, because equipment certified for a higher-risk zone can be used in a lower-risk zone, provided the gas group, temperature class and other environmental conditions also match. The reverse is not permitted: gear for zone 2 is not installed in zone 1. Check the marking and the certificate in each case, not only the equipment category.
What data is needed for a quotation on Ex control gear?
State the classified zone, gas group, temperature class, the function wanted, voltage, rated current, number of poles, material, IP rating and cable entries. For a control station, add the list of push buttons and lamps. Delivery is 24–72 h when the item is in stock, locally or at the supplier; to order, usually 1–4 weeks, and depending on brand and specification it can take longer.
What is the difference between an Ex isolator and an ordinary Ex switch?
The isolator serves to isolate a circuit visibly and safely for maintenance work and is sometimes designed for operation with no load or a reduced load, according to its utilisation category. The control switch is designed for repeated switching on and off under rated load. Check the utilisation category and the breaking current of the device against the real load.