ABB ABB ACS580-01
ABB ACS580-01 wall-mounted variable frequency drives in frame sizes R1–R9 and R9e, with rated powers from 0.75 to 355 kW on a 230 or 400 V three-phase supply.
The ACS580-01 is ABB's general-purpose industrial variable frequency drive, in the wall-mounted version. The hardware manual describes it as a drive for asynchronous motors, permanent magnet motors and synchronous reluctance motors (SynRM). Without options, the standard delivery includes the IP21 (UL Type 1) enclosure, the ACS-AP-S control panel, the choke, the internal EMC filter category C2, the Safe torque off function, a brake chopper in frame sizes R1, R2 and R3, coated boards and the multilingual installation and start-up guide.
The type is read from the drive nameplate in the form ACS580-01-xxxx-y, followed by options separated by a plus sign. The xxxx group is the size code from the power tables (for example 12A7, with a rated output current of 12.6 A), and the digit y is the voltage range: 2 for 208–240 V, 4 for 380–480 V and 6 for 525–600 V. With a request for quotation, send the full type with options (for example +B056 for IP55) and a photo of the nameplate; we confirm the code and availability in the quotation.
Models and codes
| Code | Note |
|---|---|
| ACS580-01-04A7-2 | 230 V supply, frame size R1: rated output current 4.7 A, 0.75 kW in nominal use (0.55 kW in heavy-duty). |
| ACS580-01-276A-2 | 230 V supply, frame size R8: 276 A, 75 kW in nominal use (55 kW heavy-duty). |
| ACS580-01-02A7-4 | 400 V supply, frame size R1: 2.6 A, 0.75 kW in nominal use (0.55 kW heavy-duty). |
| ACS580-01-12A7-4 | 400 V supply, frame size R1: 12.6 A, 5.5 kW in nominal use (4.0 kW heavy-duty). |
| ACS580-01-033A-4 | 400 V supply, frame size R3: 32 A, 15 kW in nominal use (11 kW heavy-duty). |
| ACS580-01-062A-4 | 400 V supply, frame size R4 (and R4 v2): 62 A, 30 kW in nominal use (22 kW heavy-duty). |
| ACS580-01-106A-4 | 400 V supply, frame size R5 (and R5 v2): 106 A, 55 kW in nominal use (45 kW heavy-duty). |
| ACS580-01-145A-4 | 400 V supply, frame size R6: 145 A, 75 kW in nominal use (55 kW heavy-duty). |
| ACS580-01-246A-4 | 400 V supply, frame size R8: 246 A, 132 kW in nominal use (110 kW heavy-duty). |
| ACS580-01-430A-4 | 400 V supply, frame size R9: 430 A, 250 kW in nominal use (200 kW heavy-duty). |
| ACS580-01-670A-4 | 400 V supply, frame size R9e: 670 A, 355 kW in nominal use (315 kW heavy-duty). |
Key specifications
| Supply voltage ranges (digit in the type) | 208–240 V (2), 380–480 V (4), 525–600 V (6) |
|---|---|
| Rated power, 230 V three-phase supply | 0.75 – 75 kW |
| Rated power, 400 V supply (digit 4) | 0.75 – 355 kW |
| Frame sizes | R1 … R9 and R9e (with variants R4 v2 and R5 v2) |
| Output frequency | 0 – 598 Hz |
| Switching frequency | 2 – 12 (R1–R5); 1.5 and 2 – 12 (R6–R9); factory value 4 kHz |
| Motor types | asynchronous, permanent-magnet, synchronous reluctance (SynRM) |
| Degree of protection | IP21 (UL Type 1) standard; IP55 (UL Type 12) with +B056; IP66 with +B063 and UL Type 4X with +B066 (sizes R1–R3); IP20 with +P940 or +P944 |
| Operating temperature | -15 … +50 (between 0 and -15 °C frost-free; derating above 40 °C at IP21) °C |
| Installation altitude | 0 – 4000 m (TN-S, TT, IT networks) or 0 – 2000 m (delta networks with a grounded corner or midpoint); derating above 1000 m |
| Maximum recommended motor cable length, 4 kHz, without external options | 100 (R1); 200 (R2); 300 (R3–R9e) m |
| Efficiency at rated power | approx. 98 %, calculated differently from IEC 61800-9-2; efficiency class IE2 per ecodesign data |
The ABB ACS580-01 hardware manual (3AXD50000044794) is revision G, valid from 25.06.2025, on ABB's official documentation server; ABB's notice on reduced sales of the ACS550 states that ACS580, ACH580 and ACQ580 have replaced the ACS550, ACH550 and ACQ550 series on the market.
Frequently asked questions
How do I read the type of an ACS580-01 from the nameplate?
The form is ACS580-01-xxxx-y, followed by options with a plus sign. The xxxx group is the size code from the power tables (for example 12A7, with 12.6 A rated output current), and the digit y is the voltage range: 2, 4 or 6. The options are read from the manual's code list, for example +B056 for IP55 or +K454 for the PROFIBUS module FPBA-01. If you have a code with options you do not recognise, you can send it to us with a photo of the nameplate; we confirm the variant in the manufacturer's documentation.
Why does the same drive have three power ratings in the table?
For each type the manual gives three sets of values: nominal use, light-duty and heavy-duty. For example, ACS580-01-145A-4 appears with 75 kW in nominal use, 75 kW light-duty and 55 kW heavy-duty. The right power depends on the duty, so it helps us to know the driven motor and the load type.
What data do I send for a quotation?
The full type with options or a photo of the nameplate, the supply voltage, the motor power and current, the motor type and the communication modules used at present. When ordering, the lead time is usually 1–4 weeks; we confirm availability and the exact lead time in the quotation.
Other ABB series
The page presents a selection from the IEC power table of the ACS580-01 hardware manual; the UL (NEC) values, derating, fuses, the 525–600 V range and dimensions are confirmed to you by code, from the manufacturer's documentation.
Updated: 2026-11-12