ABB ABB ACS880-01

ABB ACS880-01 wall-mounted frequency inverters, in frame sizes R1–R9 and R9e, with rated powers from 0.75 to 355 kW on 230, 400, 500 or 690 V supply.

ACS880-01 is the wall-mounted frequency inverter variant of the ABB ACS880 industrial family. The hardware manual describes it as a unit for induction motors, permanent magnet synchronous motors, induction servo motors and ABB synchronous reluctance motors (SynRM). The standard delivery includes the IP21 (UL Type 1) enclosure, the ACS-AP-W control panel with Bluetooth connection, the Safe torque off function, the DC choke and coated boards; the brake chopper is included on frame sizes R1–R4, while the EMC filter is not part of the standard delivery and is added as an option.

The type is read from the label of the unit in the form ACS880-01-xxxx-y, followed by options separated by a plus sign. The group xxxx indicates the current size (for example 072A for 72 A), and the digit y indicates the voltage range: 2 for 208–240 V, 3 for 380–415 V, 5 for 380–500 V and 7 for 525–690 V. For a quotation, please send us the complete type with options (for example +B056 for IP55) and a photo of the nameplate; we confirm the code and the availability in the quotation.

Models and codes

CodeNote
ACS880-01-04A6-2230 V supply, frame size R1: output current 4.6 A, 0.75 kW in nominal use (0.55 kW in heavy-duty).
ACS880-01-02A4-3400 V supply, frame size R1: 2.4 A, 0.75 kW in nominal use (0.55 kW heavy-duty).
ACS880-01-09A4-3400 V supply, frame size R1: 10.0 A, 4.0 kW in nominal use (3.0 kW heavy-duty).
ACS880-01-032A-3400 V supply, frame size R3: 32 A, 15 kW in nominal use (11 kW heavy-duty).
ACS880-01-072A-3400 V supply, frame size R5: 72 A, 37 kW in nominal use (30 kW heavy-duty).
ACS880-01-145A-3400 V supply, frame size R6: 145 A, 75 kW in nominal use (55 kW heavy-duty).
ACS880-01-246A-3400 V supply, frame size R8: 246 A, 132 kW in nominal use (110 kW heavy-duty).
ACS880-01-430A-3400 V supply, frame size R9: 430 A, 250 kW in nominal use (200 kW heavy-duty).
ACS880-01-670A-3400 V supply, frame size R9e: 670 A, 355 kW in nominal use (315 kW heavy-duty).
ACS880-01-271A-7690 V supply, frame size R9: 271 A, 250 kW in nominal use (200 kW heavy-duty).

Key specifications

Supply voltage ranges (digit in the type)208–240 V (2), 380–415 V (3), 380–500 V (5), 525–690 V (7)
Rated power, 230 V supply0.75 – 75 kW
Rated power, 400 V supply (digit 3)0.75 – 355 kW
Rated power, 690 V supply5.5 – 250 kW
Frame sizesR1 … R9 and R9e
Output frequency0 – 598 (with du/dt or sine filter: 0 – 120) Hz
Motor typesasynchronous, permanent-magnet synchronous, induction servo motor, SynRM
Degree of protectionIP21 (UL Type 1) standard; IP55 (UL Type 12) with option +B056; IP20 with +P940 or +P944
Operating temperature-15 … +55 (frost-free, with derating) °C
Installation altitude0 – 4000 m above sea level (derating above 1000 m)
Efficiency at rated powerapprox. 98 % at rated power; efficiency class IE2 (ecodesign data per IEC 61800-9-2)
Maximum recommended motor cable length150 (R1–R3); 300 (R4–R9e) m

The ABB hardware manual for ACS880-01 (3AUA0000078093) is revision V, valid from 26.02.2026, with no notice of withdrawal from the range.

Frequently asked questions

How do I read the type of an ACS880-01 from the nameplate?

The form is ACS880-01-xxxx-y, followed by options with the plus sign. The group xxxx is the current size from the power table (072A means 72 A), and the digit y is the voltage range: 2, 3, 5 or 7. The options are read from the code list in the manual, for example +B056 for IP55 or +E200 for an EMC filter category C3. If you have a code with options you do not recognise, you can send it to us with a photo of the nameplate; we confirm the variant in the manufacturer's documentation.

Why does the same unit have two powers in the table?

For each type the manual gives three sets of values: nominal use, light-duty and heavy-duty. For example, ACS880-01-072A-3 appears with 37 kW in nominal use and with 30 kW in heavy-duty mode. The power shown on the unit depends on the duty mode, so it helps us to know the motor driven and the type of load; for sizing, the manual recommends the DriveSize program.

What details do I send for a quotation?

The complete type with options or a photo of the nameplate, the supply voltage, the motor power and current, the motor type and the communication modules used now. Made to order, the lead time is usually 1–4 weeks; we confirm the availability and the exact lead time in the quotation.

Other ABB series

The listing shows a selection from the IEC power table of the ACS880-01 hardware manual, with intermediate sizes read in the manual; the UL (NEC) values, the derating and the fuses are confirmed to you by code, from the manufacturer's documentation. For the other types in the ACS880 family, which have their own manuals, we confirm the data by code, on request.

Updated: 2026-11-12