Skip to content
+40 371 232 404|Mon - Fri: 08:00 - 16:30 (Romania time)

DAB DAB EVOPLUS

DAB EVOPLUS electronic wet-rotor circulators for heating, air conditioning and domestic hot water recirculation: 3–75.6 m³/h and up to 18 m, DN32–DN100 flanges, single (B), twin (D) and bronze SAN versions.

EVOPLUS is the DAB range of electronic wet-rotor circulators for heating, ventilation and air conditioning installations in commercial buildings. The EVOPLUS version covers 3–75.6 m³/h and heads of up to 18 m, with flanged connections DN32–DN100 and port-to-port distances of 220–450 mm, in a single version (B, supplied with an insulating casing) or twin version (D, with a check valve in the discharge and a blind flange for work on one of the motors). EVOPLUS Small covers 2–12 m³/h and up to 11 m, with 1½″ or 2″ thread or DN32 and DN40 flanges, and the SAN versions have a bronze body for domestic hot water recirculation. The pump body is in cast iron 250 UNI ISO 185 with cataphoretic coating, the hydraulic impeller in technopolymer, and the permanent-magnet motor is controlled by the integrated converter, with an OLED display; the liquid can be at −10…+110 °C, and the maximum working pressure is 16 bar.

For a quotation, send us the full code from the nameplate (for example EVOPLUS B 120/250.40 M) or, for a new pump, the required flow and head, the flange diameter and the existing port-to-port distance, single or twin version, the type of installation (heating, chilled water, domestic hot water) and the control signal used (0–10 V, PWM, Modbus). When the item is in stock, locally or at the supplier, delivery takes 24–72 h; to order, typically 1–4 weeks.

Models and codes

CodeNote
EVOPLUS B 40/220.40 MSingle, DN40 PN 10, port-to-port distance 220 mm; P1 max 90 W; 4 m at zero flow; EEI ≤ 0.23.
EVOPLUS B 120/250.40 MSingle, DN40 PN 10, port-to-port distance 250 mm; P1 max 465 W; 12 m at zero flow; EEI ≤ 0.20.
EVOPLUS B 180/280.50 MSingle, DN50 PN 10, port-to-port distance 280 mm; P1 max 750 W; 17.1 m at zero flow; EEI ≤ 0.19.
EVOPLUS B 150/340.65 MSingle, DN65 PN 10, port-to-port distance 340 mm; P1 max 1,210 W; 15.2 m at zero flow; EEI ≤ 0.18.
EVOPLUS B 120/450.100 MSingle, DN100 PN 10, port-to-port distance 450 mm; P1 max 1,560 W; 12.2 m at zero flow; EEI ≤ 0.19.
EVOPLUS D 100/340.65 MTwin, DN65 PN 10, port-to-port distance 340 mm; P1 max 590 W; 10.1 m at zero flow; EEI ≤ 0.20.
EVOPLUS B 120/280.50 SAN MBronze body for domestic hot water, DN50 PN 10, port-to-port distance 280 mm; P1 max 530 W; 12 m at zero flow.
EVOPLUS 60/180 XMEVOPLUS Small with 2″ thread, port-to-port distance 180 mm; P1 max 100 W; EEI ≤ 0.20.

Key specifications

Flow3–75.6 (EVOPLUS); 2–12 (EVOPLUS Small) m³/h
Headup to 18 (EVOPLUS); up to 11 (EVOPLUS Small) m
Liquid temperature−10…+110 (glycol max. 50 %); ambient max. +40 °C °C
Maximum working pressure16 bar
Connectionsflanges DN32–DN65 PN 6/10/16 and DN80, DN100 PN 6 (4 holes); Small: 1½″ / 2″ thread or DN32, DN40 flanges
Port-to-port distance (EVOPLUS)220–450 mm
Absorbed power P1 max (EVOPLUS B/D)90–1.560 W
Energy efficiency indexEEI ≤ 0.18 … EEI ≤ 0.23 (EVOPLUS B/D)
Supply and protectionsingle-phase 220–240 V, 50/60 Hz; IP X4D (EVOPLUS) / IP 44 (Small); insulation class F

The data sheet "Electronic circulators" for the EVOPLUS range (code 60150748, edition 03/2026) is the data sheet published on the EVOPLUS page of the DAB Pumps website; the range is current. In the same family, DAB presents EVP separately, a new range of low-consumption circulators (0–11.9 m³/h, 14 m), suitable for replacing old three-speed circulators; EVOPLUS remains listed, with documentation from 2026.

Frequently asked questions

How do I read a code such as EVOPLUS B 120/250.40 SAN M?

B = single circulator (D = twin); 120 = maximum head in decimetres; 250 = port-to-port distance in mm; 40 = nominal diameter of the flanges (DN40); SAN = version for domestic hot water; M = single-phase motor. On the threaded EVOPLUS Small, X means a 2″ thread, and its absence a 1½″ thread.

Can the EVOPLUS be used on chilled water, in air conditioning?

Yes. The circulator is designed so that, with liquid colder than the room air, condensate drains away without affecting the electronic or mechanical parts. The single version comes with an insulating casing; on the twin version the insulation is provided by the installer, without blocking the condensate drain channels.

What control modes and signals does it have?

From the factory it works on proportional differential pressure (ΔP-v); it also has constant differential pressure (ΔP-c), constant curve, ΔP-c with water temperature influence and the Economy function, which reduces the set value by up to 50 %. The EVOPLUS version accepts 0–10 V, PWM and 4–20 mA signals, a temperature sensor for ΔT and Modbus over RS-485; LonBus is added with a separate module.

Other DAB series

The curves, minimum suction pressure, dimensions and weight differ from one model to another; before quotation we confirm the model, the port-to-port distance and the flanges on the exact code from the nameplate, from the DAB data sheet.

Updated: 2026-11-23