Schneider Electric Schneider Electric TeSys Deca GV2ME
Schneider Electric TeSys Deca GV2ME thermal-magnetic motor circuit breakers, with pushbuttons, thermal setting from 0.1–0.16 A to 24–32 A, for motors of up to 15 kW at 400 V.
GV2ME is the Schneider Electric range of thermal-magnetic circuit breakers for motor protection, from the TeSys Deca Frame 2 family, with pushbutton control and screw terminals. The catalogue gives them for three-phase motors from 0.06 to 15 kW at 400/415 V, in category AC-3/AC-3e, with thermal setting ranges from 0.1–0.16 A (GV2ME01) to 24–32 A (GV2ME32) and magnetic tripping Ii ± 20 % from 1.93 to 537.6 A. They conform to IEC/EN 60947-4-1 and IEC/EN 60947-2, have a rated operational voltage Ue of 690 V, are suitable for isolation, are sensitive to the loss of a phase and have IP20 on the front in open mounting.
The code shows the setting range: for example GV2ME08 is set between 2.5 and 4 A (1.1 kW motor at 400 V), and GV2ME14 between 6 and 10 A (3 kW at 400 V). For connection with lugs the digit 6 is added (GV2ME086), for spring terminals the digit 3 (GV2ME083, up to GV2ME223), and the variants with integrated auxiliary contact block have the suffixes AE1TQ, AE11TQ or AN11TQ. For a quotation, please send us the full code from the device; we check the variant in the manufacturer's catalogue before sending the quotation.
Models and codes
| Code | Note |
|---|---|
| GV2ME01 | thermal setting 0.1–0.16 A; magnetic tripping 1.93 A. |
| GV2ME04 | setting 0.40–0.63 A; 0.12 kW motor at 400/415 V; magnetic tripping 9.3 A. |
| GV2ME08 | setting 2.5–4 A; 1.1 kW motor at 400/415 V; magnetic tripping 74 A. |
| GV2ME10 | setting 4–6.3 A; 2.2 kW motor at 400/415 V; magnetic tripping 91 A. |
| GV2ME14 | setting 6–10 A; 3 kW motor at 400/415 V; magnetic tripping 149 A. |
| GV2ME16 | setting 9–14 A; 5.5 kW motor at 400/415 V; Icu 15 kA, Ics 50 %. |
| GV2ME20 | setting 13–18 A; 7.5 kW motor at 400/415 V; Icu 15 kA, Ics 50 %. |
| GV2ME32 | setting 24–32 A; 15 kW motor at 400/415 V; Icu 10 kA, Ics 50 %; magnetic tripping 537.6 A. |
Key specifications
| Motor power at 400/415 V, AC-3/AC-3e | 0.06 – 15 kW |
|---|---|
| Thermal setting ranges | 0.1–0.16 A (GV2ME01) … 24–32 A (GV2ME32) |
| Magnetic tripping Ii (± 20 %) | 1.93 – 537.6 A |
| Breaking capacity Icu at 400/415 V | > 100 kA up to GV2ME14; 15 kA on GV2ME16…GV2ME22; 10 kA on GV2ME32 |
| Rated operational voltage Ue / insulation voltage Ui (IEC 60947-2) | 690 / 690 V |
| Standards | IEC/EN 60947-4-1, IEC/EN 60947-2, UL 60947-4-1, CSA C22.2 nr. 60947-4-1 |
| Protection rating (front, open mounting) | IP20 |
| Ambient temperature | operation -20 … +60 (open mounting), -20 … +40 (in enclosure); storage -40 … +80 °C |
| Maximum operating altitude | 2000 m |
| Mechanical endurance | 100.000 manevre |
The TeSys Deca GV2ME circuit breakers (Frame 2) are in the Schneider Electric catalogue “TeSys - Catalog 2026” (MKTED210011EN, edition 08.2026), with no mention of discontinuation.
Frequently asked questions
How do I choose a GV2ME for a motor?
By the rated current on the motor nameplate: the thermal setting of the circuit breaker must include this current. For example, for 3.2 A, GV2ME08 (2.5–4 A) is chosen. Send us the nameplate data and we check the choice in the manufacturer's catalogue.
What does a suffix 3 or 6 at the end of the code mean?
In the catalogue, 3 marks the variant with spring terminals (for example GV2ME083), and 6 the variant for connection with lugs (for example GV2ME086).
What data do I send for a quotation?
The full code from the device (including any suffix), the rated current of the motor and the auxiliary contacts you need.
Other Schneider Electric series
The table covers the GV2ME circuit breakers with screw terminals from the IEC reference table of the catalogue; the values at 500 V and 690 V, the tripping curves and the GV2P range (with rotary handle) are read from the catalogue for the exact code.
Updated: 2026-11-23