Skip to content
+40 371 232 404|Mon - Fri: 08:00 - 16:30 (Romania time)

Schneider Electric Schneider Electric TeSys Deca LC1D

Schneider Electric TeSys Deca LC1D09…LC1D95 three-pole contactors, 9–95 A in AC-3/AC-3e, for motors of up to 45 kW at 400 V.

TeSys Deca LC1D is the Schneider Electric range of three-pole contactors for controlling three-phase motors, in category AC-3/AC-3e, from LC1D09 (9 A, 4 kW at 400 V) to LC1D95 (95 A, 45 kW at 400 V). Each contactor in the catalogue table has one instantaneous normally open auxiliary contact and one normally closed auxiliary contact. For non-inductive loads (AC-1) the same contactors have currents from 25 A (LC1D09, LC1D12) to 125 A (LC1D80, LC1D95). The catalogue states conformity with EN/IEC 60947-4-1, UL 60947-4-1 and CSA C22.2 No. 60947-4-1, protection rating IP20 on the front and an operating temperature from -40 to +60 °C.

The basic code (for example LC1D25) is completed with the coil voltage code: P7 means 230 V AC 50/60 Hz, M7 220 V, B7 24 V, BD 24 V DC, and BL 24 V DC low consumption. The variant with spring terminals has the digit 3 before the voltage code (LC1D093…), and the one for lugs or busbars the digit 6 (LC1D096…). For a quotation, please send us the full code from the contactor, including the coil code; we check the variant in the manufacturer's catalogue before sending the quotation.

Models and codes

CodeNote
LC1D099 A in AC-3/AC-3e, 4 kW at 380/400 V, 25 A in AC-1; 1 NO + 1 NC contact.
LC1D1212 A in AC-3/AC-3e, 5.5 kW at 380/400 V, 25 A in AC-1.
LC1D1818 A in AC-3/AC-3e, 7.5 kW at 380/400 V, 32 A in AC-1.
LC1D2525 A in AC-3/AC-3e, 11 kW at 380/400 V, 40 A in AC-1.
LC1D3232 A in AC-3/AC-3e, 15 kW at 380/400 V, 50 A in AC-1.
LC1D50A50 A in AC-3/AC-3e, 22 kW at 380/400 V, 80 A in AC-1; EverLink power connections with hexagon socket screws.
LC1D65A65 A in AC-3/AC-3e, 30 kW at 380/400 V, 80 A in AC-1; EverLink power connections.
LC1D9595 A in AC-3/AC-3e, 45 kW at 380/400 V, 125 A in AC-1.

Key specifications

Rated current AC-3/AC-3e (up to 440 V)9 – 95 A
Motor power at 380/400 V, AC-3/AC-3e4 – 45 kW
AC-1 current (non-inductive loads, θ ≤ 60 °C)25 – 125 A
Instantaneous auxiliary contacts1 NO + 1 NC
AC coil codes 50/60 HzB7 24 V, F7 110 V, M7 220 V, P7 230 V, U7 240 V, Q7 380 V, V7 400 V (and others, in the catalogue)
DC coil codesJD 12 V, BD 24 V, ED 48 V, FD 110 V, MD 220 V; consum redus: BL 24 V, EL 48 V (LC1D09…D38)
StandardsEN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 nr. 60947-4-1
Protection rating (front)IP20
Ambient temperatureoperation -40 … +60; storage -60 … +80 °C
Altitude without derating3000 m
Mounting35 mm rail or with screws (LC1D09…D80A); 35 or 75 mm rail (LC1D80, D95 AC)

The TeSys Deca LC1D contactors are in the Schneider Electric catalogue “TeSys - Catalog 2026” (MKTED210011EN, edition 08.2026), with no mention of discontinuation.

Frequently asked questions

What does “P7” or “BD” at the end of the LC1D code mean?

It is the coil voltage code: P7 = 230 V AC 50/60 Hz, M7 = 220 V AC, B7 = 24 V AC, BD = 24 V DC, BL = 24 V DC low consumption (DC coils of this type are for LC1D09…D38 and LC1D80/D95; on LC1D40A…D65A the variants from the Deca Advanced range are used). For example LC1D18P7 is an 18 A contactor in AC-3 with a 230 V AC coil.

What is the difference between LC1D80 and LC1D80A?

There are two different contactors in the catalogue: LC1D80A has EverLink power connections and 66 A in AC-3/AC-3e (37 kW at 400 V), and LC1D80 has 80 A in AC-3/AC-3e (37 kW at 400 V) and 125 A in AC-1. Send us the exact code and we confirm the replacement.

What data do I send for a quotation?

The full code from the contactor (including the coil code), the type of terminals (screw, spring or for lugs) and, if you need them, additional auxiliary contacts.

Other Schneider Electric series

The table values come from the reference tables of the catalogue for the TeSys Deca three-pole contactors; the curves, the electrical endurance and the dimensions are read from the catalogue for the exact code. The TeSys Deca Advanced contactors (with AC/DC coil) and the four-pole variants have their own tables in the same catalogue.

Updated: 2026-11-23