Siemens Siemens SENTRON 3VA
SENTRON 3VA1 moulded case circuit breakers (thermal-magnetic releases, 16–1,000 A for line protection) and 3VA2 (ETU electronic trip units, 25–1,600 A: 25–1,250 A in sizes 3VA20–3VA26, 800–1,600 A on 3VA27), with Icu at 380–415 V of up to 110 kA on 3VA1 and 150 kA on 3VA2 (200 kA in class E, with ETU from series 3 and 8), depending on size and class.
SENTRON 3VA is the Siemens range of moulded case circuit breakers. The 3VA1 series has a thermal-magnetic (TM) trip unit and, in the Siemens catalogue, is presented for standard applications in infrastructure and industrial installations, in 1-, 2-, 3- or 4-pole variants, with sizes from 100 A (3VA10) to 1,000 A (3VA15). The 3VA2 series has electronic trip units (ETU) and is presented for demanding applications, with high breaking capacity, good selectivity and additional functions, such as integrated measurement and connection to a communication system; sizes 3VA20–3VA26 cover 25–1,250 A, and 3VA27 completes the range up to 1,600 A. Both series operate without derating up to +50 °C.
The breaking capacity is chosen by classes (for example M, H, C), and the Icu value depends on the voltage and the size. For a quotation, send us the full code from the breaker (for example 3VA2116-6HL32-0AA0 or 3VA1340-5EF32-0AA0), the rated current and Icu required, the number of poles, the type of trip unit and the fitted accessories (auxiliary contacts, auxiliary releases, rotary mechanism, motor operator); we confirm the exact code in the quotation.
Models and codes
| Code | Note |
|---|---|
| 3VA1025-3ED32-0AA0 | 3VA10 (size 100), class N, 3 poles, TM210 (FTFM) thermal-magnetic trip unit; In 25 A, Ir 25 A fixed, Ii 12.8 × In fixed; Icu = Ics 25 kA at 415 V; 130 × 76.2 × 70 mm (height × width × depth), mass 0.918 kg; IP40 on the front. |
| 3VA1116-6ED32-0AA0 | 3VA11 (size 160), class H, 3 poles, TM210 (FTFM); In 160 A, Ir 160 A fixed, Ii 10 × In fixed; Icu = Ics 70 kA at 415 V; mass 1.003 kg. |
| 3VA1340-5EF32-0AA0 | 3VA13 (size 400), class M, 3 poles, TM240 (ATAM); In 400 A, Ir 280–400 A, Ii 5–10 × In; Icu = Ics 55 kA at 415 V; 248 × 138 × 110 mm, mass 4.852 kg. |
| 3VA2025-5HL32-0AA0 | 3VA20 (size 100), class M, 3 poles, ETU320 (LI); In 25 A, Ir 10–25 A, Ii 1.5–12 × In; Icu = Ics 55 kA at 415 V; 181 × 105 × 86 mm, mass 2.088 kg. |
| 3VA2110-5JP32-0AA0 | 3VA21 (size 160), class M, 3 poles, ETU550 (LSI); In 100 A, Ir 40–100 A, Isd 0.6–10 × In, Ii 1.5–12 × In; Icu = Ics 55 kA at 415 V; mass 2.147 kg. |
| 3VA2116-6HL32-0AA0 | 3VA21 (size 160), class H, 3 poles, ETU320 (LI); In 160 A, Ir 63–160 A, Ii 1.5–10 × In; Icu = Ics 85 kA at 415 V; mass 2.103 kg. |
| 3VA2225-7HL32-0AA0 | 3VA22 (size 250), class C, 3 poles, ETU320 (LI); In 250 A, Ir 100–250 A, Ii 1.5–10 × In; Icu = Ics 110 kA at 415 V; mass 2.175 kg. |
| 3VA2580-6HL32-0AA0 | 3VA25 (size 1000), class H, 3 poles, ETU320 (LI); In 800 A, Ir 320–800 A, Ii 1.5–10 × In; Icu = Ics 85 kA at 415 V; 320 × 210 × 120 mm, mass 13.375 kg. |
Key specifications
| 3VA1: sizes and rated current In (at 50 °C) | 3VA10: 100 A (16–100 A); 3VA11: 160 A (16–160 A); 3VA12: 250 A (160–250 A); 3VA13: 400 A (320–400 A); 3VA14: 630 A (500–630 A); 3VA15: 1.000 A (630–1.000 A) |
|---|---|
| 3VA2: sizes and rated current In | 3VA20: 100 A (25–100 A); 3VA21: 160 A (25–160 A); 3VA22: 250 A (160–250 A); 3VA23: 400 A (250–400 A); 3VA24: 630 A (400–630 A); 3VA25: 1.000 A (630–1.000 A); 3VA26: 1.250 A; 3VA27 (completare): 800–1.600 A |
| Rated operational voltage Ue (AC, 50/60 Hz) and insulation voltage Ui | 3VA1: Ue 690 V, Ui 800 V on 3 and 4 poles; Ue 415 V, Ui 500 V on 1 and 2 poles (3VA11); 3VA20–3VA26: Ue 690 V, Ui 800 V |
| 3VA1: Icu at 380–415 V, by class (3 and 4 poles) | 3VA10: B 16 kA, N 25 kA, S 36 kA; 3VA11: N 25 kA, S 36 kA, M 55 kA, H 70 kA; 3VA12: S 36 kA, M 55 kA, H 70 kA; 3VA13 and 3VA14: S 36 kA, M 55 kA, H 70 kA, C 110 kA; 3VA15: M 55 kA, H 70 kA, C 110 kA |
| 3VA2: Icu at 380–415 V, by class | 3VA20: M 55 kA, H 85 kA, C 110 kA, L 150 kA; 3VA21–3VA24: M 55 kA, H 85 kA, C 110 kA, L 150 kA, E 200 kA (class E only with ETU from series 3 and 8); 3VA25 and 3VA26: M 55 kA, H 85 kA, C 110 kA |
| 3VA1: trip units | thermal-magnetic TM210 (FTFM), TM220 (ATFM) and TM240 (ATAM) for line protection; TM120M (AM) for starter protection; availability depends on size |
| 3VA2: trip units | electronic ETU: series 3 (ETU310M, ETU320, ETU330, ETU340 ELISA, ETU350, ETU350M), series 5 (ETU550, ETU550M, ETU560) and series 8 (ETU850, ETU860, ETU860M); availability depends on size |
| Mechanical endurance (cycles) | 3VA10–3VA14: 20,000; 3VA15: 10,000; 3VA20–3VA22: 25,000; 3VA23 and 3VA24: 20,000; 3VA25 and 3VA26: 10,000 |
| Operating temperature | without derating up to +50 °C (3VA1 and 3VA2) |
The Siemens page of the moulded case circuit breaker range and the data sheet “SENTRON 3VA MCCBs – key specifications” (May 2026) present SENTRON 3VA1 and 3VA2 as the current offer; the values per size come from the extract “Catalog Extract from LV 10 · 10/2023”, and the 3VA product data sheets from Siemens Industry Mall for the models in the table (as of 22.11.2026) do not mark the codes as withdrawn or as spare parts.
Frequently asked questions
What is the difference between 3VA1 and 3VA2?
Siemens describes 3VA1 as a breaker for standard applications, with a thermal-magnetic trip unit, and 3VA2 for demanding applications, with high breaking capacity, electronic trip units (ETU), good selectivity and additional functions. At 380–415 V, Icu reaches 110 kA on 3VA1 (class C, sizes 3VA13–3VA15) and 150 kA on 3VA2 (class L); class E, of 200 kA, exists on sizes 3VA21–3VA24 only with ETU trip units from series 3 and 8.
What does the digit before the letters, after the first hyphen, in the code show?
It encodes the breaking capacity Icu at 415 V: on 3VA2, 5 means 55 kA, 6 means 85 kA, 7 means 110 kA, 8 means 150 kA and 0 means 200 kA; on 3VA1, 2 means 16 kA, 3 means 25 kA, 4 means 36 kA, 5 means 55 kA, 6 means 70 kA and 7 means 110 kA. For example, 3VA2116-6HL32-0AA0 has Icu 85 kA at 415 V, and 3VA1116-6ED32-0AA0 has 70 kA.
What do I need to send you for a quotation?
The full code from the breaker, for example 3VA2116-6HL32-0AA0, the rated current and Icu needed, the number of poles, the trip unit and the fitted accessories. We confirm the exact code in the quotation, including for variants with ETU5 or ETU8 or with another number of poles.
Other Siemens series
The values per size and class come from the Siemens catalogue extract LV 10 · 10/2023, and those per code from the product data sheets of the models in the table; we confirm Icu at 500–690 V, the setting ranges and the dimensions of other 3VA codes for the exact code, before the quotation.
Updated: 2026-11-23