Siemens Siemens SINAMICS G120
SINAMICS G120 modular frequency converter system (Control Unit and Power Module), from 0.37 kW to 250 kW; models in the table: PM240-2 Power Module in frame sizes FSA–FSF (3–110 kW at low overload, 380–480 V) and CU240E-2 Control Unit.
SINAMICS G120 is, in the Siemens technical documentation, a modular converter system: two functional units, the Control Unit (control, monitoring, communication with the controller) and the Power Module (motor supply), to which an operator panel can be added. The standard G120 range covers 0.37–250 kW in frame sizes FSA–FSG. The G120C and G120X converters are distinct families, not variants of the modular system: G120C is compact, and G120X has a separate catalogue.
For a quotation, send us the full codes of both modules from the nameplate, for example Power Module 6SL3210-1PE23-3UL0 and Control Unit 6SL3244-0BB12-1PA1, the mains voltage, the motor power or current, the bus type (PROFIBUS DP or PROFINET) and the desired operator panel; on that basis we confirm the suitable combination.
Models and codes
| Code | Note |
|---|---|
| 6SL3210-1PE18-0UL1 | PM240-2 Power Module without filter, with integrated braking chopper, FSA, 380–480 V; 3 kW at low overload (7.7 A output) and 2.2 kW at high overload (5.9 A); 196 × 73 × 165 mm, 1.40 kg. |
| 6SL3210-1PE21-8UL0 | PM240-2 Power Module without filter, with integrated braking chopper, FSB, 380–480 V; 7.5 kW at low overload (18 A output) and 5.5 kW at high overload (13.2 A); 3.00 kg. |
| 6SL3210-1PE23-3UL0 | PM240-2 Power Module without filter, with integrated braking chopper, FSC, 380–480 V; 15 kW at low overload (32 A output) and 11 kW at high overload (26 A); 355 × 140 × 165 mm, 4.80 kg. |
| 6SL3210-1PE24-5UL0 | PM240-2 Power Module without filter, with integrated braking chopper, FSD, 380–480 V; 22 kW at low overload (45 A output) and 18.5 kW at high overload (38 A); 472 × 200 × 237 mm, 16.00 kg. |
| 6SL3210-1PE28-8UL0 | PM240-2 Power Module without filter, with integrated braking chopper, FSE, 380–480 V; 45 kW at low overload (90 A output) and 37 kW at high overload (75 A); 551 × 275 × 237 mm, 26.00 kg. |
| 6SL3210-1PE32-1UL0 | PM240-2 Power Module without filter, with integrated braking chopper, FSF, 380–480 V; 110 kW at low overload (205 A output) and 90 kW at high overload (178 A); 708 × 305 × 357 mm, 61.00 kg. |
| 6SL3244-0BB12-1PA1 | CU240E-2 DP Control Unit, type E, Safety Integrated STO, PROFIBUS DP; 6 DI, 3 DO (2 relay, 1 transistor), 2 AI, 2 AO, PTC/KTY interface, USB and SD/MMC interfaces; without Power Module and without panel; 199 × 73 × 46 mm, 0.49 kg. |
| 6SL3244-0BB12-1FA0 | CU240E-2 PN Control Unit, type E, Safety Integrated STO, PROFINET; 6 DI, 3 DO (2 relay, 1 transistor), 2 AI, 2 AO, PTC/KTY interface, USB and SD/MMC interfaces; without Power Module and without panel; 199 × 73 × 46 mm, 0.49 kg. |
Key specifications
| Structure | modular system: Control Unit (CU) and Power Module (PM), plus optional operator panel (BOP-2 or IOP-2) |
|---|---|
| Standard G120 range | 0.37–250 kW, frame sizes FSA–FSG, according to the Siemens technical documentation, Catalog D 31.1 |
| Control Units presented in the technical documentation | CU230P-2 (pumps, fans, compressors), CU240E-2 (general machines), CU250S-2 (demanding speed, positioning) |
| PM240-2 Power Module supply (models in the table) | 3 AC 380–480 V, 47–63 Hz |
| Rated power (PM240-2 models in the table) | 3–110 kW at low overload (LO); 2.2–90 kW at high overload (HO) |
| Rated output current (PM240-2 models in the table) | 7.7–205 A at LO; 5.9–178 A at HO |
| Overload capacity (300 s cycle) | LO: 110 % for 57 s and 150 % for 3 s, at –10…+40 °C (FSA–FSC) or –20…+40 °C (FSD–FSF); HO: 150 % for 57 s and 200 % for 3 s, at –10…+50 °C (FSA–FSC) or –20…+50 °C (FSD–FSF) |
| Output frequency (PM240-2, models in the table) | 0–200 Hz with vector control; 0–550 Hz with V/f control |
| Frame sizes, mass and protection (PM240-2 models in the table) | FSA–FSF; 1.40–61.00 kg; IP20 / UL open type, without Control Unit and without panel |
The Siemens Industry Mall product data sheets of the models in the table do not mark the articles as withdrawn. The presentation of the system, of the 0.37–250 kW range and of the table of PM240-2 Power Modules comes from the Siemens technical documentation “SINAMICS G120 standard converters”, Catalog D 31.1, edition October 2021 with update May 2022, published on the official Siemens documentation server; we confirm the current edition of the data for the exact code, before the quotation.
Frequently asked questions
Are G120, G120C and G120X the same converter?
No. In the Siemens technical documentation (Catalog D 31.1), SINAMICS G120 standard is the modular system made up of a Control Unit and a Power Module, from 0.37 kW to 250 kW, in frame sizes FSA–FSG. SINAMICS G120C is a distinct family of compact converters, from 0.55 kW to 132 kW. SINAMICS G120X is intended for HVAC, water and wastewater applications, from 0.75 kW to 630 kW, and has a separate catalogue (D 31.5). The full code from the nameplate shows which one it is.
What must be ordered for a G120 converter?
The system is chosen in two or three steps: Power Module, Control Unit and, optionally, an operator panel. The PM240-2 Power Module is offered without an integrated line filter (the code ends in UL0 or UL1) or with an integrated class A filter (AL0 or AL1), according to the table in the technical documentation; the Control Unit is chosen according to the inputs and outputs needed, the safety functions and the bus type, for example CU240E-2 DP (PROFIBUS DP) or CU240E-2 PN (PROFINET).
What do low overload (LO) and high overload (HO) mean on PM240-2?
The Siemens data sheets state two power ratings for the same Power Module, depending on the duty cycle: for example 6SL3210-1PE23-3UL0 has 15 kW at low overload (LO) and 11 kW at high overload (HO). Tell us the duty cycle of the motor or the power and current from the nameplate, and we confirm the Power Module for the exact code.
Other Siemens series
The table values come from the product data sheets of the models and from the documentation indicated; for other voltages, variants with an integrated filter, other Control Units or other frame sizes, we confirm the data on the exact code, before the quotation.