Skip to content
+40 371 232 404|Mon - Fri: 08:00 - 16:30 (Romania time)

Wilo Wilo-TOP-S

Wilo glandless single circulation pumps with manually stepped speed control, for hot water heating, air conditioning, closed cooling circuits and industrial circulation.

Wilo-TOP-S is a single, glandless circulation pump: all rotating parts are in contact with the pumped liquid, which also lubricates the plain bearings of the rotor shaft. The speed is selected manually, in steps (3 steps; 2 steps on 1~ pumps with P2 ≥ 350 W), and the casing has a cataphoretic coating (KTL) that protects it against corrosion caused by condensate. Wilo lists it for hot water heating systems of any kind, industrial circulation systems, air conditioning systems and closed cooling circuits. The variant with two motor-pump units in the same casing is TOP-SD, presented on its own separate page.

The code has the form TOP-S 40/10: 40 is the nominal diameter of the connection, and 10 is the nominal head, in metres, at zero flow. The connection is threaded on sizes 25 and 30 and flanged, from DN 40 to DN 100, on the others; the supply is 1~230 V or 3~400 V, depending on the type. For a quotation we need the full code from the nameplate, the supply voltage and the working pressure of the installation. When the item is in stock, locally or at the supplier, delivery takes 24–72 h; to order, typically 1–4 weeks.

Models and codes

CodeNote
TOP-S 25/5Threaded connection G 1½, installation length 180 mm, 10 bar; 1~230 V and 3~400 V variants.
TOP-S 25/13Threaded connection G 1½, installation length 180 mm, 10 bar; liquid -20…+110 °C (exception to the general limit).
TOP-S 30/10Threaded connection G 2, installation length 180 mm, 10 bar; 1~230 V and 3~400 V variants.
TOP-S 40/10Combined flange DN 40, installation length 250 mm, PN 6/10; the 1~230 V variant has 2 speed steps, a 3~400 V variant also exists.
TOP-S 50/15Combined flange DN 50, installation length 340 mm, PN 6/10, 3~400 V only.
TOP-S 65/15Combined flange DN 65, installation length 340 mm, PN 6/10, 3~400 V only.
TOP-S 80/7DN 80 flange, installation length 360 mm; 6 bar in the standard variant, 10 bar in one of the 3~400 V variants; the 1~230 V variant has 2 speed steps.

Key specifications

Liquid temperature-20…+130 °C, for a short time (2 h) up to +140 °C; TOP-S 25/13, TOP-S 80/15 and TOP-S 80/20: -20…+110 °C; with the Wilo-Protect C module: -20…+110 °C
Ambient temperature-20…+40 °C
Supply1~230 V, 50 Hz (depending on type); 3~230 V, 50 Hz (with optional switching plug); 3~400 V, 50 Hz
Speed controlmanual, 3 steps (2 steps on 1~ pumps with P2 ≥ 350 W)
Maximum working pressure6/10 bar or 6 bar in the standard version, 10 bar in a special version
Connectionsthreaded (G 1½ and G 2) or flanged (DN 40–DN 100), depending on type, for pipes from Rp 1 to DN 100; DN 40–DN 65: combined flange PN 6/10; DN 80 and DN 100: PN 6 flange
Installation length180–360 mm, depending on type (the variants in the list on the series page)
Weight4.4–31 kg, depending on type (the variants in the list on the series page)
Materialsgrey cast iron casing, plastic rotor, stainless steel shaft, metal-impregnated carbon bearing
Permitted liquidsheating water according to VDI 2035; water-glycol mixtures, maximum ratio 1:1 (with glycol, the pumping data are corrected for the higher viscosity)

The series page on the Wilo website lists 48 TOP-S variants, with G 1½ and G 2 connections and DN 40–DN 100 flanges, with no mention of discontinuation; the installation and operating instructions Wilo-TOP-S/-SD/-RL/-I, edition 2026-03 (code 2165760), are published on the same page.

Frequently asked questions

What do the figures in the TOP-S 40/10 code mean?

40 is the nominal diameter of the connection (DN 40), and 10 is the nominal head, in metres, at zero flow. For a quotation, send us the full code from the nameplate.

How is the speed adjusted on TOP-S?

Manually, in steps: 3 steps, or 2 steps on 1~ pumps with P2 ≥ 350 W. The selected step is shown on the pump, and on three-phase models a lamp indicates the direction of rotation.

Can I use TOP-S for drinking water or food?

No. The Wilo instructions state that, because of the materials used, the series is not suitable for drinking water or food products; the permitted liquids are heating water according to VDI 2035 and water-glycol mixtures, in a ratio of at most 1:1.

Other Wilo series

Variants, voltages and nominal pressure differ from one code to another; we confirm the data for the exact code from the nameplate before the quotation.

Updated: 2026-11-23