Grundfos Grundfos SCALA2
Grundfos SCALA2 compact booster sets, type 3-45 (nominal flow 3 m³/h, maximum head 45 m), self-priming, with an integrated frequency inverter and adjustable constant pressure, for water pressure boosting in light commercial buildings; the 1 × 200–240 V, 50/60 Hz variants come with a plug or with a cable without a plug.
Grundfos SCALA2 is a compact, "all-in-one" booster set for water pressure boosting in light commercial buildings: the self-priming multistage pump, the water-cooled permanent magnet motor, the frequency inverter, the pressure sensor and the pressure vessel form a single unit. The sensor in the pump discharge compares the measured pressure with the desired one, and the inverter changes the speed to keep the pressure constant at the taps; the default pressure is 3 bar. The datasheet describes a single type, SCALA2 3-45, with a nominal flow of 3 m³/h and a maximum head of 45 m; the variants differ in supply voltage and plug type, each with its own product number.
For a quotation, send us the full designation from the pump nameplate (for example SCALA2 3-45) and the product number or, if it is missing, the supply voltage and plug type (Schuko, no plug, UK, NEMA), as well as the application: supply from the mains, from a roof tank, from a buried tank or from a shallow well, with the level difference on the suction side. When the item is in stock, locally or at the supplier, delivery takes 24–72 h; to order, typically 1–4 weeks.
Models and codes
| Code | Note |
|---|---|
| SCALA2 3-45, cod 93013252 | 1 × 200–240 V, 50/60 Hz, with Schuko plug; maximum head 45 m, nominal flow 3 m³/h. |
| SCALA2 3-45, cod 93013254 | 1 × 200–240 V, 50/60 Hz, without plug; maximum head 45 m, nominal flow 3 m³/h. |
| SCALA2 3-45, cod 93013322 | 1 × 200–240 V, 50/60 Hz, with UK plug; maximum head 45 m, nominal flow 3 m³/h. |
| SCALA2 3-45, cod 93013250 | 208–230 V, 60 Hz, with NEMA 6-15 plug; maximum head 45 m, nominal flow 3 m³/h. |
| SCALA2 3-45, cod 93013251 | 115 V, 60 Hz, with NEMA 5-15 plug; maximum head 45 m, nominal flow 3 m³/h. |
Key specifications
| Type and performance | SCALA2 3-45: nominal flow 3 m³/h; maximum head 45 m; performance curves comply with ISO 9906, grade 2B |
|---|---|
| Pressure | maximum system pressure 10 bar (1 MPa); maximum inlet pressure 6 bar (0.6 MPa); default set pressure 3 bar |
| Temperature | pumped liquid max. 45 °C; ambient temperature max. 55 °C at 1 × 200–240 V, 50/60 Hz and 45 °C on the 208–230 V and 115 V, 60 Hz variants |
| Power supply | 1 × 200–240 V, 50/60 Hz: Imax 2.8 A, P1 550 W, standby power 2 W; variants of 208–230 V, 60 Hz (2.8 A) and 115 V, 60 Hz (4.9 A) |
| Connections, dimensions and weight | R 1 connections (NPT 1" on the NPT variant); H1 302 mm, L1 403 mm, W1 193 mm; weight 10 kg; the inlet and outlet connections can be adjusted by up to 5° |
| Protection and noise | IP X4D (outdoor installation); noise level of 44 dB(A), measured in a typical application (constant pressure of 2.5 bar, flow of 1 m³/h) |
| Pumped liquid | clean, thin water, with pH 4–9; maximum chloride content 300 ppm; maximum free chlorine 1.0 ppm |
| Materials | pump housing and stator in aluminium, composite material and EN 1.4301 / AISI 304; carbon/ceramic shaft seal; chamber pack (four stages) in composite material; pressure vessel in composite material, butyl and EN 1.4301 / AISI 304 |
| Protection functions | dry-run protection (active by default, cannot be disabled); micro-leak detection (off by default); maximum continuous running time 30 min (active by default); current- and temperature-dependent motor protection |
The data come from the Grundfos datasheet "SCALA Multistage centrifugal boosters, 50/60 Hz" (code 99735562, ECM 1455603, edition 07.2026, 36 pages), published on the official Grundfos documentation server. The datasheet covers SCALA1 and SCALA2 together; only the data dedicated to SCALA2 are used, and the product numbers are those in the "SCALA2 50/60 Hz" table of the datasheet. The exact variant, by voltage and plug type, is confirmed on the product number.
Frequently asked questions
What is the difference between SCALA2 and SCALA1?
According to the datasheet, SCALA2 has an integrated frequency inverter and adjustable constant pressure, a noise level of 44 dB(A) in a typical application (2.5 bar, 1 m³/h) and can pump water with pH 4–9 (chlorides up to 300 ppm). SCALA1 has Bluetooth communication, an external input and a "twin" function, a noise level of 55 dB(A) and pH 4–7 (chlorides up to 50 ppm). If the application requires an external input or twin operation, we can discuss the SCALA1 variant on request.
Can it be installed on suction, or only with inlet pressure?
SCALA2 is self-priming, and the datasheet recommends the SCALA range also for shallow wells (8 m); in the selection guide, SCALA2 has a medium suitability for wells and for the buried tank, because SCALA1 has better suction. The inlet pipe must have a diameter larger than 1" if it is longer than 10 m or if the suction lift exceeds 4 m. At positive inlet pressure, the pump may produce a clicking noise, in which case the locking pin can be fitted; with the pin fitted, the self-priming function is not available, and at negative inlet pressure the pin must be removed.
What data should I send to identify the exact variant?
The designation from the nameplate (SCALA2 3-45), the product number, the supply voltage and the plug type, because the same hydraulic performance exists in variants with a Schuko, UK, NEMA plug or without a plug. The voltage and frequency must match the mains: the 1 × 200–240 V variants work at 50/60 Hz, and the 115 V (code 93013251) and 208–230 V (code 93013250) variants in the table are for 60 Hz; the datasheet also lists 100–115 V variants for 50/60 Hz.
Other Grundfos series
We confirm the SCALA2 variant from the product number, the supply voltage, the plug type and the suction conditions of the installation, before the quotation.
Updated: 2026-11-23