Electric heat tracing and pipe heating
Electric heat tracing is a heating system made up of a heating cable run along a pipe, tank or valve, under the thermal insulation, to compensate for the heat losses of the installation. It maintains the temperature of a fluid or prevents it from freezing. A complete system comprises the cable, connection and termination kits, temperature sensors and a thermostat or controller.
Cables are chosen by technology. A self-regulating cable has a conductive polymer core whose resistance rises with temperature, so the output falls by itself as the pipe warms up; it can be cut to length on site and can usually cross over itself without local overheating. A constant-power cable gives the same output per metre, almost independent of the pipe temperature, and is used for longer lengths and higher temperatures. A mineral-insulated cable has a metal sheath and magnesium oxide insulation, withstands high temperatures and outputs, but is made to the length measured for the route.
Control is by a thermostat with a sensor on the pipe or by an electronic controller with several circuits, alarms and temperature limiting. In explosive atmosphere zones, the system must meet the requirements of the IEC/IEEE 60079-30 series (electrical resistance trace heating in explosive atmospheres), and the maximum cable surface temperature is chosen below the temperature class of the zone. Also relevant are the output per metre, the maximum circuit length at the available voltage, the maximum exposure temperature, the mechanical and chemical protection of the sheath and the residual current protection of the circuit.
How to choose
Purpose of the system: frost protection or maintaining process temperature
Frost protection needs little power, to keep the fluid above freezing point at the minimum ambient temperature; maintaining a viscous fluid or a solution that crystallises needs more power and finer control.
Heat losses of the pipe
They are calculated from the pipe diameter and material, the type and thickness of the insulation, the difference between the maintenance temperature and the minimum ambient temperature, and from valves and supports, with a safety factor; wet or missing insulation cancels any calculation.
Cable type: self-regulating, constant-power or mineral-insulated
A self-regulating cable adapts to routes with crossings and valves, a constant-power one covers longer lengths and higher temperatures, and a mineral-insulated one is chosen for high temperatures and outputs.
Maximum exposure temperature
The temperature reached during steam cleaning, when the cable is de-energised, is also taken into account, because some cables lose their properties above their exposure limit.
Hazardous area and temperature class
In an explosive atmosphere, cables and accessories suited to the zone are chosen, according to the IEC/IEEE 60079-30 series, and the temperature at the cable surface must stay below the temperature class of the atmosphere.
Circuit length, voltage and cold-start current
With self-regulating cables, the current drawn at cold start is higher than in steady state, so the maximum circuit length depends on the start-up temperature and on the protection used.
Control and monitoring
A simple thermostat is enough for frost protection, but sensitive processes call for a controller with a sensor, a temperature alarm and, where needed, monitoring of several circuits from a single place.
What to send for a quotation
- The fluid in the pipe and the temperatures: maintenance, minimum ambient and maximum exposure
- Diameter, material and length of the pipe, plus the number of valves and supports
- Type and thickness of the thermal insulation and whether the route is indoors or outdoors
- Hazardous area, gas group and temperature class, if applicable
- Available voltage and power, plus the preferred cable or controller type
- Required quantity and, if available, the route sketch
Typical applications
- Frost protection of water pipes
- Maintaining the temperature of viscous fluids
- Heating of tanks and process vessels
- Instrumentation lines and valves
Maintenance and spare parts
Heating cables are covered by the thermal insulation, so they are usually checked electrically, not visually: insulation resistance to earth, continuity and current drawn are compared with the values measured at commissioning. Frequent faults are wet or damaged insulation, improperly sealed connection kits and end terminations, and mechanical damage to the cable during work on the pipe. Sensors and controllers are functionally tested before the cold season, and the residual current protection is tested periodically.
Brands we quote for this product type
Frequently asked questions
What is the difference between a self-regulating cable and a constant-power one?
A self-regulating cable reduces its own output as the temperature rises, is cut to length on site and usually tolerates crossing over itself. A constant-power cable gives the same output per metre, is made to set lengths and is used on long routes or at higher temperatures. The choice depends on the route, the maintenance temperature and the complexity of the valves; for short routes with many valves, the self-regulating cable is usually preferred.
How is the required output per metre of pipe determined?
The heat loss per metre is calculated from the pipe diameter, the type and thickness of the insulation and the difference between the maintenance temperature and the minimum ambient temperature, and then a safety factor is added. Valves, supports and uninsulated sections need extra cable length or higher local output. The result is rounded up to the available cable output, and for fluids sensitive to overheating, the maximum temperature at the cable surface is also checked.
Can electric heat tracing be used in hazardous (explosive) areas?
Yes, but only with cables, connection kits and controllers suited to the classification of the zone and meeting the requirements of the IEC/IEEE 60079-30 series. The maximum temperature at the cable surface must stay below the temperature class of the atmosphere. For each route, the zone, gas group and temperature class are specified. Not every cable suits every zone, so the choice is confirmed against the classification documentation of the installation.
What should a heat tracing quotation request contain, and how is delivery made?
The fluid and temperatures, the pipe and insulation data, the available voltage and, where applicable, the Ex zone and the list of valves are needed. Delivery is 24–72 h when the item is in stock, locally or at the supplier; otherwise it is brought in to order, typically 1–4 weeks, and depending on brand and specifications it can take longer.