Danfoss Danfoss VLT® HVAC Drive FC 102
Danfoss VLT® HVAC Drive FC 102 frequency converters for fans, pumps and compressors in buildings, from 1.1 kW to 1,400 kW (depending on the mains voltage), with Fire Emergency Mode, an integrated Smart Logic controller and 0–590 Hz output.
The FC 102 is the drive in the Danfoss VLT® HVAC Drive range that the product sheet describes as suitable for pumps, fans and compressors in buildings. It has functions dedicated to HVAC applications: four PID controllers with auto-tuning, a Smart Logic controller with 4 independent loops, date- and time-based functions, and protocols for building management systems (FC Protocol, Metasys N2, FLN Apogee, Modbus RTU and BACnet MSTP, all built in). The selection guide describes Fire Emergency Mode, which keeps the fan running instead of stopping the drive for self-protection, including the multi-zone version, for smoke extraction and stairwell pressurisation; full-load operation is stated for at least one hour at 70 °C ambient temperature (80 % load at high power ratings), with support for EN 12101. On fans, the series offers resonance bypass (up to 4 speed ranges), no-load or broken-belt warning and multi-motor operation; on pumps, a cascade controller, dry-run protection, no-flow or low-flow detection, sleep mode and flow compensation. The mains supplies covered are 1 × 200–240 V, 3 × 200–240 V, 380–480 V, 525–600 V and 525–690 V.
The type code starts with FC-102, followed by the power (for example P11K for 11 kW), the mains voltage (T4 = 3 × 380–480 V AC; T2, T6 and T7 for the other three-phase supplies), the enclosure protection (E20 = IP20, E21 = IP21/Type 1, E55 = IP55/Type 12, E66 = IP66/Type 4X), the RFI filter (H1 = class A1/B (C1)) and the letters for brake and fuse, LCP panel, board coating, mains options, software version, panel language and options A (fieldbus), B, C and D; Danfoss states that not all combinations are possible. For a quotation, send us the full type code from the drive's nameplate; if you do not have it, send the motor power and current, the mains voltage, the required degree of protection and the communication protocol of the building management system. When the item is in stock, locally or at the supplier, delivery takes 24–72 h; to order, typically 1–4 weeks.
Models and codes
| Code | Note |
|---|---|
| FC-102P1K1T4 | 1.1 kW, 3 × 380–480 V; 3 A continuous, 3.3 A intermittent (60 s) at 380–440 V; enclosure A2 (IP20/IP21) or A4/A5 (IP55/IP66). |
| FC-102P5K5T4 | 5.5 kW, 3 × 380–480 V; 13 A continuous, 14.3 A intermittent (60 s) at 380–440 V; enclosure A3 (IP20/IP21) or A5 (IP55/IP66). |
| FC-102P11KT4 | 11 kW, 3 × 380–480 V; 24 A continuous, 26.4 A intermittent (60 s) at 380–440 V; enclosure B3 (IP20) or B1 (IP21/IP55/IP66). |
| FC-102P22KT4 | 22 kW, 3 × 380–480 V; 44 A continuous, 48.4 A intermittent (60 s) at 380–440 V; enclosure B4 (IP20) or B2 (IP21/IP55/IP66). |
| FC-102P45KT4 | 45 kW, 3 × 380–480 V; 90 A continuous, 99 A intermittent (60 s) at 380–440 V; enclosure C3 (IP20) or C1 (IP21/IP55/IP66). |
| FC-102P90KT4 | 90 kW, 3 × 380–480 V; 177 A continuous, 195 A intermittent (60 s) at 380–440 V; enclosure C4 (IP20) or C2 (IP21/IP55/IP66). |
| FC-102P5K5T2 | 5.5 kW, 3 × 200–240 V; 24.2 A continuous, 26.6 A intermittent (60 s); enclosure B3 (IP20) or B1 (IP21/IP55/IP66). |
| FC-102P11KT6 | 11 kW, 3 × 525–600 V; 18 A continuous, 20 A intermittent (60 s); enclosure B3 (IP20) or B1 (IP21/IP55/IP66). |
Key specifications
| Power | 1.1–22 kW (1 × 200–240 V); 1.1–160 kW (3 × 200–240 V); 1.1–1.000 kW (3 × 380–480 V); 1.1–90 kW (3 × 525–600 V); 1.1–1.400 kW (3 × 525–690 V) |
|---|---|
| Supply voltage | 200–240 V, 380–480 V, 525–600 V, 525–690 V, ±10 %, 50/60 Hz |
| Output frequency | 0–590 Hz |
| Degree of protection | IP00 (355–1,200 kW), IP20 (1.1–800 kW), IP21 (1.1–1,400 kW), IP54 (75–1,400 kW), IP55 and IP66 (1.1–90 kW) |
| Output current, enclosures A–C | 3–177 A continuous at 3 × 380–440 V, for 1.1–90 kW (normal overload: 110 % for 1 min in 10 min) |
| Basic inputs/outputs | 6 digital inputs (two configurable as digital outputs and two usable as pulse inputs), 2 analogue inputs (voltage 0…+10 V or current 0/4–20 mA), 1 analogue output 0/4–20 mA, 2 relays |
| Integrated communication | FC Protocol, Metasys N2, FLN Apogee, Modbus RTU, BACnet MSTP |
| Motor cable length, enclosures A–C | 150 m ecranat / 300 m neecranat |
| Ambient temperature, enclosures A–C | maximum 50 °C at rated continuous current; maximum 55 °C with derating (in SFAVM switching mode) |
The Danfoss product sheet "VLT® HVAC Drive FC 102" (AM424146072894en-US0201, July 2023) and the series selection guide (DKDD.PB.102.B2.02, November 2020) are published on Danfoss's official documentation servers, in the same library as the operating guide for enclosures A–C, 1.1–90 kW (AQ267037536117en-US2202, July 2025).
Frequently asked questions
What does Fire Emergency Mode do?
The selection guide describes the mode as a safety function that prevents the drive from stopping for self-protection: the fan keeps running for smoke extraction or stairwell pressurisation. The drive can run with the normal settings, in which the mode suppresses alarms, or with special settings, up to 32 variants in 4 groups. The multi-zone version allows different speeds depending on the zones where the fire is active, and an operating log records the mode and the alarms.
What current and enclosure does an FC-102P11KT4 have?
The FC-102P11KT4 is rated 11 kW at 3 × 380–480 V, with 24 A continuous at 380–440 V (21 A at 441–480 V). The enclosure is B3 in IP20 or B1 in IP21, IP55 and IP66. The values come from the normal-overload table (110 % for 1 min in 10 min).
Can the FC 102 be connected to a building management system?
Yes. The product sheet lists built-in protocols (FC Protocol, Metasys N2, FLN Apogee, Modbus RTU, BACnet MSTP) and optional cards for PROFIBUS DP, DeviceNet, LonWorks, BACnet, PROFINET, EtherNet/IP, Modbus TCP and BACnet/IP.
Other Danfoss series
The currents and enclosures given are taken from the selection guide tables for enclosures A, B and C (1.1–90 kW, 110 % normal overload); for higher power ratings (enclosures D, E and F), for 12-pulse versions and for the exact combination of options, we confirm the data in the Danfoss documentation for the full type code before quotation.