Danfoss Danfoss VLT® AQUA Drive FC 202
Danfoss VLT® AQUA Drive FC 202 frequency converters for pumps in water and wastewater applications, from 0.25 kW to 1,400 kW (depending on the mains voltage), with dry-run detection, pipe fill mode, check valve ramp and a pump cleaning function (deragging).
The FC 202 is the drive in the Danfoss VLT® AQUA Drive range, optimised for AC motors driving pumps in water and wastewater applications. The selection guide groups the dedicated functions as follows: end-of-curve and dry-run detection, no-flow or low-flow detection, advanced sleep mode with boost function, flow compensation, initial and final ramp (protection for the pump's thrust bearings), pipe fill mode against water hammer, check valve ramp, flow confirmation and pre/post lubrication. In wastewater installations, the "deragging" function reverses the pump's direction of rotation when it detects the start of clogging (reactive mode) or at set intervals (preventive mode). Several pumps can be controlled through the digital cascade controller, with Hot Swap, or through the MCO 101 and MCO 102 options. Danfoss indicates 110 %, 150 % or 160 % of current for 1 minute, depending on power and parameters, and the range also includes single-phase versions: 1 × 200–240 V and 1 × 380–480 V.
The type code starts with FC-202, followed by the power (for example P22K for 22 kW), the mains voltage (T4 = 3 × 380–480 V AC; S2 and S4 = single-phase supplies of 200–240 V and 380–480 V respectively; T2, T6 and T7 for the other three-phase supplies), the enclosure protection (E20 = IP20, E21 = IP21/Type 1, E55 = IP55/Type 12, E66 = IP66/Type 4X), the RFI filter and the special-version position (SXXX for standard software; LXX1 for the digital cascade controller, LX1X for condition monitoring); Danfoss states that not all combinations are possible. For a quotation, send us the full type code from the drive's nameplate; if you do not have it, send the rated power and current of the pump motor, the mains voltage and number of phases, the required degree of protection and the number of pumps to be controlled. When the item is in stock, locally or at the supplier, delivery takes 24–72 h; to order, typically 1–4 weeks.
Models and codes
| Code | Note |
|---|---|
| FC-202PK37T4 | 0.37 kW, 3 × 380–480 V; 1.3 A continuous, 1.4 A intermittent (60 s) at 380–440 V; enclosure A2 (IP20) or A4/A5 (IP55/IP66). |
| FC-202P4K0T4 | 4 kW, 3 × 380–480 V; 10 A continuous, 11 A intermittent (60 s) at 380–440 V; enclosure A2 (IP20) or A4/A5 (IP55/IP66). |
| FC-202P7K5T4 | 7.5 kW, 3 × 380–480 V; 16 A continuous, 17.6 A intermittent (60 s) at 380–440 V; enclosure A3 (IP20) or A5 (IP55/IP66). |
| FC-202P22KT4 | 22 kW, 3 × 380–480 V; 44 A continuous, 48.4 A intermittent (60 s) at 380–440 V; enclosure B4 (IP20) or B2 (IP21/IP55/IP66). |
| FC-202P55KT4 | 55 kW, 3 × 380–480 V; 106 A continuous, 117 A intermittent (60 s) at 380–440 V; enclosure C3 (IP20) or C1 (IP21/IP55/IP66). |
| FC-202P90KT4 | 90 kW, 3 × 380–480 V; 177 A continuous, 195 A intermittent (60 s) at 380–440 V; enclosure C4 (IP20) or C2 (IP21/IP55/IP66). |
| FC-202P7K5S4 | 7.5 kW, single-phase supply 1 × 380–480 V; output of 16 A continuous, 17.6 A intermittent (60 s) at 380–440 V; input current 33 A at 400 V; enclosure B1 (IP21/IP55/IP66). |
| FC-202P1K1S2 | 1.1 kW, single-phase supply 1 × 200–240 V; output of 6.6 A continuous, 7.3 A intermittent (60 s); input current 12.5 A; enclosure A3 (IP20) or A5 (IP55/IP66). |
Key specifications
| Power | 1.1–22 kW (1 × 200–240 V); 7.5–37 kW (1 × 380–480 V); 0.25–160 kW (3 × 200–240 V); 0.37–1.000 kW (3 × 380–480 V); 0.75–90 kW (3 × 525–600 V); 11–1.400 kW (3 × 525–690 V) |
|---|---|
| Supply voltage | 1 × 200–240 V, 1 × 380–480 V, 3 × 200–240 V, 3 × 380–480 V, 3 × 525–600 V, 3 × 525–690 V, 50/60 Hz |
| Output frequency | 0–590, depending on power Hz |
| Overload | 110 %, 150 % or 160 % of current for 1 minute, depending on power and parameter settings |
| Degree of protection | IP20, IP21, IP54, IP55, IP66, depending on power; all power ratings are available in IP54/IP55 |
| Output current, enclosures A–C | 1.3–177 A continuous at 3 × 380–440 V, for 0.37–90 kW (normal overload: 110 % for 1 min in 10 min) |
| Basic inputs/outputs | 6 digital inputs (two configurable as digital outputs and two usable as pulse inputs), 2 analogue inputs (voltage or current 0/4–20 mA), 1 analogue output 0/4–20 mA, 2 relays |
| Integrated communication | FC Protocol and Modbus RTU |
| Ambient temperature | –25…+50 °C without derating, up to 315 kW; up to 55 °C with derating |
The selection guide "VLT® AQUA Drive FC 202 series", 0.25 kW – 1.4 MW (AD396832756475en-US0101, April 2024) is published on Danfoss's official documentation server, alongside the product sheet "VLT® AQUA Drive FC 202" (DKDD.PFP.201.A7.02, June 2020), published on Danfoss's official download server.
Frequently asked questions
What does the "deragging" function mean and when is it used?
It is a pump protection function from the Danfoss selection guide: the drive monitors the power absorbed at the shaft in relation to the flow. In reactive mode, at the start of clogging, it reverses the pump's direction of rotation in a flushing cycle; in preventive mode, it makes the same reversal at set intervals. The guide notes that wastewater installations benefit in particular from this function.
Why does the same power code appear with two different currents?
The selection guide gives separate tables for normal overload (110 % for 1 min in 10 min) and for high overload (160 %). At 3 × 380–480 V, code P11K appears with 11 kW and 24 A in the first case and with 7.5 kW and 16 A in the second. Tell us the rating required, so that we identify the correct code.
Can the FC 202 be supplied from a single-phase mains?
Yes, there are S2 (1 × 200–240 V, 1.1–22 kW) and S4 (1 × 380–480 V, 7.5–37 kW) versions, with three-phase output for the motor. For example, the FC-202P7K5S4 is rated 7.5 kW, with 16 A on the output and 33 A on the input at 400 V.
Other Danfoss series
The currents and enclosures given are taken from the selection guide tables for enclosures A, B and C (up to 90 kW); for higher power ratings (enclosures D, E and F), for 12-pulse versions and for the exact combination of options and licences, we confirm the data in the Danfoss documentation for the full type code before quotation.